Updated November 4, 2026 · 240-volt, single-phase heaters · How we check

A 9 kW sauna heater draws 37.5 amps at 240 volts. That means a 40-amp breaker, or a 50-amp breaker if your inspector treats the heater as a continuous load (sized at 125%). A 6 kW heater draws 25 amps: a 30-amp or 35-amp breaker. Your heater's manual and your local code decide which.

Some makers list a different breaker than this math. A licensed electrician must confirm what your home needs.

Breaker and wire size for each heater size

HeaterAmps at 240 VBreaker: next size upCopper wire for that breakerAmps × 125% (continuous load)Breaker at 125%Copper wire for that breaker
4.5 kW18.8 A20 A12 AWG23.4 A25 A10 AWG
6 kW25.0 A30 A10 AWG31.3 A35 A8 AWG
8 kW33.3 A35 A8 AWG41.7 A45 A8 AWG (6 AWG if NM cable)
9 kW37.5 A40 A8 AWG46.9 A50 A8 AWG (6 AWG if NM cable)
10.5 kW43.8 A45 A8 AWG (6 AWG if NM cable)54.7 A60 A6 AWG (4 AWG if NM cable)
12 kW50.0 A50 A8 AWG (6 AWG if NM cable)62.5 A70 A4 AWG

How each number is worked out: amps = watts ÷ 240. "Next size up" is the next standard breaker size (NEC 240.6) at or above the amps. The 125% columns multiply the amps by 1.25 first, the rule for loads that run 3 hours or more; whether it applies to your sauna heater is your inspector's call. Wire: the smallest copper size whose rating in NEC Table 310.16 covers the breaker (75°C column for wire in conduit, 60°C for NM house cable), with 12 AWG capped at 20 amps and 10 AWG at 30 amps (NEC 240.4(D)). These follow the 2023 National Electrical Code; your city may use a different edition or add its own rules.

What heater makers actually list

The manual for your exact heater is the rule your electrician and inspector follow. Two we've read:

  • HUUM Drop 6 kW: the manual lists a 30-amp breaker and 10 AWG wire (25 amps at 240 volts). That's smaller than the 35 amps the 125% math above gives, so follow the manual and ask your electrician.
  • Harvia Cilindro PC90E (9 kW): the manual gives 37.5 amps on one circuit, or 25 amps per circuit if split into two, but doesn't list a breaker size.

Also check before you buy

  1. Room in your electrical panel for a 2-pole breaker of that size, and enough total service. A 9 kW heater is roughly what an electric dryer and an oven use together.
  2. Heat-rated wire inside the sauna room. Many manuals require high-temperature wire for the last run to the heater; ordinary cable isn't allowed in the hot room.
  3. Hardwired, not plugged in. Most heaters of 4.5 kW and up are wired in; Harvia's Cilindro manual says plugs and pigtails are not allowed.
  4. A permit. Most cities require one for a new 240-volt circuit.